Silence; Auto Silence - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Programming
Release Stage NAC
If Release Stage Coded, Release Stage Discharge or Release Stage Pre-Discharge is selected as the
Output Type, the following subscreen will be displayed:
An NAC can be used to signal the stages of a release operation. This screen allows the programmer
to select the NAC output that will indicate the release stages for Release Circuit 1 or Release
Circuit 2. For a description of this feature, refer to "Release Stage/NAC Operation" on page 85.

Silence

OUTPUT #
1=SILENCE
NON-SIL
Pressing 1 while viewing Output Screen #2 will cause the following screen to be displayed:
2=AUTO SILENCE NO
3=SIL INHIBITED NO
Output Screen #2
Pressing 1 while viewing the Silenceable Screen #1 will program the selected Output as a
silenceable circuit. This will allow the Output to be silenced by pressing the Alarm Silence key or
by the Auto Silence feature.
Pressing 2 while viewing the Silenceable Screen #1 will program the selected Output as a
nonsilenceable circuit. This will prevent the selected main circuit board Output from being silenced
by pressing the Alarm Silence key or by the Auto Silence feature.
Pressing 3 while viewing the Silenceable Screen #1 will program the selected Output for Stage
Silenceable. This option is used for Release Stage NACs or cross-zone coding NACs. These NACs
will be non-silenceable until its associated Release Circuit has finished discharging, after which the
NAC will become silenceable.
Pressing 1 while viewing the Silenceable Screen #2 will program the selected Output as a
synchronized mute circuit. Refer to "Synchronized NAC Operation" on page 62 for a description of
synchronization.
Important: When an Output Circuit with a mix of audible and visual devices is programmed for
Sync Mute, only the audible devices will be turned off if the Silence key is pressed or if the
Autosilence feature is enabled. The visual devices (strobes, etc.) will continue to operate.
NOTE:
Option will not be available and the display will indicate N/A next to it.

Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press
screens will be displayed:
1=NO
2=5 MINUTES
3=10 MINUTES
60
SILENCEABLE
1=SILENCEABLE
2=NON SILENCEABLE
3=STAGE SILENCEABLE
Silenceable Screen #1
If the Output Circuit has been programmed as a Releasing Circuit, the Silenceable
AUTO SILENCE
Auto Silence Screen #1
RELEASE STAGES
1=RELEASE 1 ONLY
2=RELEASE 2 ONLY
SILENCEABLE
1=SYNC MUTE
Silenceable Screen #2
while viewing Output Screen #2. The following
2
AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #2
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Master Programming Level
AUTO SILENCE
1=30 MINUTES