Programming
Output Circuit Map
INPUT ZONE #
1=OUTPUT CIRCUIT MAP
Output Mapping (per input zone). allows the programmer/operator to assign the Output Circuits
2=FREEZE SUPV.
NO
that will be activated when a particular Input Zone or cross-zoned releasing group goes active.
Edit Input Zone Screen #3
Pressing 1 for Output Circuit Map while viewing Edit Input Zone Screen #3 will display screens
which show the Output Circuits programmed to activate when the selected Input Zone (or cross-
zoned releasing group) is activated. Output Map Screen #1 displays the Output Type Codes and
programming for Output Circuits 1 through 3 and Output Map Screen #2 displays the Output Type
Code and programming for Output Circuit 4.
As an example, if Template 1 has been selected as the FACP Configuration [refer to "FACP
CONFIG (Application Templates)" on page 53], selecting the Output Circuit Map for Input Zone 1
will display the following screens:
The screens indicate that when Input Zone 1 is activated:
Note that the MAP may indicate that an Input Zone is programmed to a particular Output Circuit
but, if it is cross-zoned with one or more other Input Zones, all must be active in order to activate
the Output Circuit. Refer to the examples in "Circuit Mapping and Cross-Zoning" on page 95.
The Output Circuit Map can be customized by selecting or deselecting any of the four output
circuits for activation. Pressing the number key corresponding to the selected output will toggle the
display between Yes for activation by the Input Zone to No for no activation. The new customized
programming is automatically saved as it is entered into the control panel.
Freeze Supervision
Pressing 2 for Freeze Supervision while viewing Edit Input Zone Screen #3, will program the
FACP to supervise the devices connected to the selected zone for a temperature freeze condition.
Each press of the 2 key will toggle the display between Freeze Supv. Yes and No. The factory
default setting is No Freeze Supervision.
Adjective/Noun
INPUT ZONE #
1=ADJECTIVE/NOUN
The Adjective/Noun selection allows the programmer to enter specific descriptors about the
2=DESCRIPTION

detector currently being programmed. Pressing 1 while viewing Edit Input Zone Screen #3 will
Edit Input Zone Screen #4
cause the following screen to be displayed:
56
OUTPUT MAP ZONE 1
1=RELEASE 1
2=HORN NAC
3=ALARM NAC
Output Map Screen #1
• Output Circuit #1 default programmed as Release 1 will activate (Yes)
• Output Circuit #2 default programmed as Horn NAC will activate (Yes)
• Output Circuit #3 default programmed as Alarm NAC will not activate (No)
• Output Circuit #4 default programmed as Alarm NAC will activate (Yes)
OUTPUT MAP ZONE 1
YES
4=ALARM NAC
YES
NO
Output Zone Screen #2
1=STANDARD ADJECTIVE
2=STANDARD NOUN
✱✱✱✱✱✱✱✱✱✱✱✱✱✱✱✱✱✱✱✱
Adjective/Noun Screen
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Master Programming Level
YES