Honeywell MRP-2002 Instruction Manual page 93

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Calculating the System Current Draw
Table 5.3 contains three columns for calculating current draws. For maximum output current avail-
able per circuit and per panel, refer to Section 1.2, "Specifications", on page 14. For each column,
calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the
totals from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 94.
Calculation Column 1
Device Type
Primary, Non-Fire Alarm Current
Qty
Main Circuit Board
1
CAC-5X
[
]
4XTMF
[
]
(1 max.)
ANN-SEC Card
[
]
(1 max.)
ANN-80(C)
[
]
ANN-I/O
[
]
ANN-RLY
[
]
ANN-(R)LED
[
]
ANN-S/PG
[
]
2-wire Detector
[
]
Heads
4-wire Detector
[
]
Heads
Power Supervision
[
]
5
Relays
NAC #1
NAC #2
NAC #3
NAC #4
Current Draw from
TB9 (nonalarm)
6
Sum each column
Primary Non-Alarm =
for totals
1 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps.
2 The current shown represents one zone (IDC) on the main circuit board in alarm. One zone consumes 0.040
amps.
3 Refer to the Device Compatibility Document for standby current.
4 Enter the number of IDCs used minus one.
5 Must use compatible listed Power Supervision Relay.
6 Total current draw listed above cannot exceed 7.2 amps
MRP-2002 Series Instruction Manual — P/N 53049:E5 7/28/2016
Secondary, Fire Alarm Current
(amps)
X[current draw]= Total
Qty
X[0.095]=
0.095
X[0.001]=
[
X[0.005]=
[
X[0.003]=
[
(1 max.)
X[0.037]=
[
X[0.035]=
[
X[0.015]=
[
X[0.028]=
[
X[0.045]=
[
3
X[
]
=
[
X[
]3=
[
X[0.025]=
[
[
[
[
]=
Secondary Alarm =
Table 5.3 System Current Draw Calculations
Calculation Column 2
(amps)
X [current draw] = Total
1
1, 2
0.221
X[0.221]
=
]
X[0.001]=
]
X[0.011]1=
]
X[0.003]=
]
X[0.040]=
]
X[0.200]=
]
X[0.075]=
]
X[0.068]=
]
X[0.045]=
4
]
X[0.040]=
]4
X[0.040]=
]
X[0.025]=
]
X[
]=
]
X[
]=
[
]=
Power Supply Calculations
Calculation Column 3
Secondary, Non-Fire Alarm Current
(amps)
Qty
X[current draw]=
1
X[0.095]=
[
]
X[0.001]=
[
]
X[0.005]=
[
]
X[0.003]=
(1 max.)
[
]
X[0.015]=
[
]
X[0.035]=
[
]
X[0.015]=
[
]
X[0.028]=
[
]
X[0.045]=
[
]
X[
]3=
[
]
X[
]3=
[
]
X[0.025]=
[
]=
Secondary Non-Alarm =
Total
0.095
93