Section 1: Product Description; Product Features - Honeywell MRP-2002 Instruction Manual

Agent release control system six-zone releasing fire control panel
Hide thumbs Also See for MRP-2002:
Table of Contents

Advertisement

Section 1: Product Description

The MRP-2002 is a six zone FACP for single and dual hazard agent releasing applications. The
FACP provides reliable fire detection, signaling and protection for commercial, industrial and insti-
tutional buildings requiring agent-based releasing. The FACP is compatible with System Sensor's i
detectors which are conventional smoke detectors that can transmit a maintenance trouble signal to
the FACP indicating the need for cleaning and a supervisory 'freeze' signal when the ambient tem-
perature falls below the detector rating of approximately 45
lation and Maintenance Instructions). In addition, the control panel is compatible with conventional
input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, water-
flow devices, tamper switches and other normally-open contact devices. Refer to Device Compati-
bility Document for a complete listing of compatible devices.
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing solenoids.
Three programmable Form-C relays (factory programmed for Alarm, Trouble and Supervisory)
and 24 VDC special application resettable and nonresettable power outputs are also included on the
main circuit board. The FACP supervises all wiring, AC voltage, battery charger and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will
activate audible and visual signaling devices, illuminate an indicator, display alarm information on
the panel's LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate
an optional module used to notify a remote station or initiate an auxiliary control function.
The MRP-2002C is a ULC approved Canadian version of the FACP which offers the same features
as the MRP-2002 but is supplied standard with a dress panel and one built-in ANN-LED annuncia-
tor.
The MRP-2002E offers the same features as the MRP-2002 but allows connection to 220/240 VAC.
Unless otherwise specified, the information in this manual applies to all versions of the panel.

1.1 Product Features

Six programmable Style B (Class B) IDCs (Initiating Device Circuit)
Four programmable Style Y (Class B) output circuits - (special application power)
Three programmable Form-C relays
7.0 amps total 24 VDC output circuit current
Resettable and non-resettable output power
Built-in Programmer
ANN-BUS for connection to optional:
ANN-80 Remote LCD Annunciator
ANN-I/O LED Driver
ANN-S/PG Printer Module
ANN-RLY Relay Module
ANN-LED Annunciator Module
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History log with 256 event storage
Control Buttons
ACK (Acknowledge)
Alarm Silence
System Reset/Lamp Test
Drill