Resynchronization
(v)
Even when any of the IEDs is taken out-of-service, the other IEDs except the out-of-service
IEDs can operate the differential protection function, in which case the logic of out-of-service
detection is provided.
As for the operation of two IEDs on a line, suppose an IED is taken out-of-service, another
IED can continue to operate the differential protection function with the local current data. It
is required that another IED is neither the master nor the slave.
On the other hand, when an IED on a three-terminal line is taken out-of-service,
synchronized sampling is established between the remaining two IEDs; hence, the two IEDs
keeps operating the differential protection function.
Note: If the master IED is taken out-of-service, one of the slave IEDs takes over the
master IED synchronized sampling function and enables the differential
protection function operates between the remaining IEDs. If the slave IED is
taken out-of-service, the master and another slave IED can maintain operating
the differential protection function.
Topology of telecommunication
2.36.3
The DIF_COMM function has two topologies for telecommunication network: a peer-to-peer
connection and a star connection. The peer-to-peer connection is used in a two-terminal line
(dual mode), whereas the star connection is used in a three-terminal line (star mode).
Dual mode
(i)
When an application is applied for a two-terminal line, the application may operate in the dual
mode between the IEDs. As illustrated in Figure 2.36-9, each IED is connected with two
bidirectional channels. The second channel provides a redundancy as a backup line with
automatic switchover, if the first channel is lost. As a result, it's possible to continue sampling
and calculating simultaneously at each other. For the dual mode, the user should set the
scheme switch [TERM_TOPOLOGY] =2Term-Dual.
CH1
IED G
CH2
Figure 2.36-9 Dual communication mode
- 503 -
Channel 1
CH1
IED H
Channel 2
CH2
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)