Table 4.9-5 Mapping points for the reception of control commands
Signal Number
Signal Name
513001 7004016D08
DEV01_CONTROL_REQ
513001 7004026D08
DEV02_CONTROL_REQ
513001 7004036D08
DEV03_CONTROL_REQ
...
...
513001 7004186D08
DEV24_CONTROL_REQ
Signal Number
Signal Name
522001 000A011001
CBK_STATE
522001 000A021001
ICB_STATE
5A0001 0008001F41
DCB RCV OR
5A0001 0008001F40
Traveling OR
4A0001 8300001B6F
GEN. TRIP
5A0001 3108003F40
SDCEN
5A0101 3100001F43
SERI_ERR
570001 3103011DA2
ASEQ_MULTI_SEL
Table 4.9-7 PLC connection points Interlock for P1, P2, and P3-control
Signal Number
Signal Name
570001 3104011DA0
TPOS1-P1
570001 3104021DA0
TPOS2-P1
570001 3104031DA0
TPOS3-P1
...
...
570001 3104181DA0
TPOS24-P1
570001 3104011DA2
TPOS1-P2
570001 3104021DA2
TPOS2-P2
570001 3104031DA2
TPOS3-P2
570001 3104181DA2
TPOS24-P2
570001 3104011DA4
TPOS1-P3
570001 3104021DA4
TPOS2-P3
570001 3104031DA4
TPOS3-P3
...
...
570001 3104181DA4
TPOS24-P3
Table 4.9-8 PLC connection points (Input signals for select condition logic)
Signal Number
Signal Name
513001 800401EE61
TPOS01IN_TMP_24
513001 800402EE61
TPOS02IN_TMP_24
513001 800403EE61
TPOS03IN_TMP_24
...
...
513001 800418EE61
TPOS24IN_TMP_24
513001 810401EE62
TPOS01IN_TMP_25
513001 810402EE62
TPOS02IN_TMP_25
513001 810403EE62
TPOS03IN_TMP_25
...
...
513001 810418EE62
TPOS24IN_TMP_25
513001 820401ED50
TPOS01IN_TMP_21
513001 820402ED50
TPOS02IN_TMP_21
Description
TPOS01 control command received. (Mapping Data)
TPOS02 control command received. (Mapping Data)
TPOS02 control command received. (Mapping Data)
...
TPOS24 control command received. (Mapping Data)
Table 4.9-6 Input signals to condition logic
Description
Command Blocking status ( Off / Blocked)
Interlock bypassing switch
Double Command Blocking (DCB) is in progress.
Travelling events are detected.
General trip
(This is setting of CMNCTRL)
Serious Error detected
Automatic sequence control is in progress.
Description
Interlock condition for P1 control in TPOS01.
Interlock condition for P1 control in TPOS02
Interlock condition for P1 control in TPOS03
...
Interlock condition for P1 control in TPOS24
Interlock condition for P2 control in TPOS01.
Interlock condition for P2 control in TPOS02
Interlock condition for P2 control in TPOS03
Interlock condition for P2 control in TPOS24
Interlock condition for P3 control in TPOS01.
Interlock condition for P3 control in TPOS02
Interlock condition for P3 control in TPOS03
...
Interlock condition for P3 control in TPOS24
Description
TPOS01 additional failure condition(PLC#1)
TPOS02 additional failure condition(PLC#1)
TPOS03 additional failure condition(PLC#1)
...
TPOS03 additional failure condition(PLC#1)
TPOS01 user configurable select condition(PLC#2)
TPOS02 user configurable select condition(PLC#2)
TPOS03 user configurable select condition(PLC#2)
...
TPOS24 user configurable select condition(PLC#2)
TPOS01 control hierarchy condition(PLC#3)
TPOS02 control hierarchy condition(PLC#3)
- 928 -
6F2S1914 (0.49)
M/O
M
M
M
M
M/O
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
M/O
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
M/O
O
O
O
O
O
O
O
O
M
M
GRL200 (Soft 033 & 037)