Toshiba GR200 Series Instruction Manual page 869

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Receiving "Select command On" from the local-end
(iii)
Figure 4.8-5 outlines the reception of the Select command 'On' from the local-end.
Wait for a command
Select stage
Select command On from the remote-end
Select command Off from the remote-end
Select command On from the local-end
Signal reception
from the front panel
Select command Off from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Figure 4.8-5 Outline of Select command 'On'
Input signal generated at the local-end
Figure 4.8-6 shows the Select logic when "Select command On (Local-ON-Control)" signal is
applied to the DPOS01 function. The signal is provided when an "On" key is pressed on the
IED front panel; the user is not required to take account of mapping. Note that the user should
set the scheme switch [DPOS01-CTRAHMI] to SBO when operation from the IED front panel
is required, we discuss how to set this in chapter
Output signal to BO
When the "select condition" signal is true, the DPOS01 function can issue a "Select success"
signal at the output-point "DPOS01_OSL_BO_CSF".
Note: The "DPOS01_OSL_BO_CSF" signal is the same as the signal shown in Figure
4.8-2. If the input signal "Local-ON-Control" is not true, the DPOS01 function
returns to the "Wait for a command" stage.
Failed
Select
Select logic
decision
- 846 -
Signal output
Success
User interface: Control sub-menu
6F2S1914 (0.49)
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
.
GRL200 (Soft 033 & 037)