Toshiba GR200 Series Instruction Manual page 136

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

In ZG, this function provides the compensation factors for all elements and these factors
are defined with settings. For example, for Z1G, the settings [Z1G-Krs], [Z1G-Kxs], [Z1G-Krm],
[Z1G-Kxm] are provided. Where, "s" refers to the protected line; the resistance "r"; the
reactance "x" reflect its property and "m" refers to a mutual circuit line for parallel line
applications.
Table 2.10-3 ZG compensation factors in lines
Element
Settings for Protected line
Z1G
Z1XG
[Z1XG-Krs], [Z1XG-Kxs]
Z2G
Z3G
Z4G
Z5G
Measuring the positive-sequence impedance to the fault point is necessary. Therefore, for
a single circuit line, the current input to the earth fault-measuring element is compensated by
the residual current (3I 0 ) of the protected line.
On the other hand, for a double circuit line, the current input is compensated by the
residual current (3I 0 ) of the protected line and residual current (3I 0 ') of the adjacent line.
Generally, the following equation is used to compensate the zero-sequence voltage drop,
in this example for the case of phase "a".
where,
Va:
Phase "a" voltage
Ia:
Phase "a" current
I
:
Zero-sequence current of the protected line
0
I
:
Zero-sequence current of the adjacent line
0m
Z
:
Positive-sequence impedance (Z
1
Z
:
Zero-sequence impedance (Z
0
Z
:
Zero-sequence mutual impedance (Z
om
Equation (2.10-32) can be presented as follows:
[Z1G-Krs], [Z1G-Kxs]
[Z2G-Krs], [Z2G-Kxs]
[Z3G-Krs], [Z3G-Kxs]
[Z4G-Krs], [Z4G-Kxs]
[Z5G-Krs], [Z5G-Kxs]
Va = (Ia − ��
) × Z1 + ��
0
- 113 -
Settings for Parallel line
[Z1G-Krm], [Z1G-Kxm]
[Z1XG-Krm], [Z1XG-Kxm]
[Z2G-Krm], [Z2G-Kxm]
[Z3G-Krm], [Z3G-Kxm]
[Z4G-Krm], [Z4G-Kxm]
[Z5G-Krm], [Z5G-Kxm]
× ��
+ ��
× ��
0
0
0��
0��
= R
+ jX
)
1
1
1
= R
+ jX
)
0
0
0
= R
+ jX
om
om
6F2S1914 (0.49)
(2.10-32)
)
om
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading

Table of Contents