Toshiba GR200 Series Instruction Manual page 292

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Reset time of DT
(vi)
In the DT characteristic, the reset time is designed to be instant.
Summary of OCN operation
(vii)
Table 2.17-4 shows a summary for OCN operation. Note that DEF will be set unconditionally
in IEC-NI, VI, EI and UK-LTI characteristics (†).
Table 2.17-4 Type and standard board in the OCN1 (A tick represents a selectable function)
Characteristics
DT
IEC-NI
IEC-VI
IEC-EI
UK LTI
IEEE-MI
IEEE-VI
IEEE-EI
US-CO2
US-CO8
Original
DEF
DEP
Threshold value
2.17.3
The value of threshold current at which the OCN (I 2 ) element will pick-up is configured by
settings; the setting [OCN1] is provided for both the IDMT and the DT characteristic. Note
that the settings of the threshold levels are allowed to have distinct values in the respective
OCN elements. A rating current for the input is defined either 1A or 5A; the input rating is
defined on a VCT. (For more information about the VCT, see Chapter
Transformer module for AC analogue input
Reset Ratio
2.17.4
The ratio of the threshold current for pick-up to reset is applied using a setting; for example,
the ratio for the OCN1 element is set using the setting [OCN1-DPR]. The reset ratios for the
other OCN elements are also provided.
Miscellaneous functions
2.17.5
DT
IEC-NI
IEC-VI
IEC-EI
✓†
✓†
✓†
N.A
N.A
N.A
N.A
N.A
N.A
N.A
IDMT
UK-LTI
IEEE-MI
IEEE-VI
✓†
).
- 269 -
6F2S1914 (0.49)
IEEE-EI
US-CO2
US-CO8
Technical description:
GRL200 (Soft 033 & 037)
Original

Advertisement

Table of Contents
loading