Toshiba GR200 Series Instruction Manual page 698

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

it is in operation. For more information of the ASEQ function, see Chapter
and monitoring application: Automatic sequence control function
Note: To know the input and output points of the DPSY02 logic, see Table 4.2-6 and
††
Table 4.2-10.
Output signal to BO
The DPSY01 function, in Figure 4.2-4, can issue a "Select success" signal at the output point
"DPSY01_FSL_BO_FLG" when the DPSY01 function determines that the "Selection command
Open (Remote-Open-Control)" signal is true. If the DPSY01 function determines that the
"Remote-Open-Control" signal is not true, the DPSY01 function returns to the "Wait for a
command" stage.
Receiving "Select command Closing" from the local-end
(iii)
Figure 4.2-5 outlines the reception of the select command 'Closing' from the local-end.
Wait for a command
Select stage
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Signal reception
from the front panel
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
Figure 4.2-5 Outline of select command for 'Closing'
Input signal generated at the local-end
Figure 4.2-6 shows the select logic when a "Select command Closing (Local-Closing-Control)"
signal is applied to the DPSY01 function. The signal is provided when a "Selection for Closing"
key is pressed on the IED front panel; the user is not required to map the signal from the
IEC61850 communication. Note that the user should set the scheme switch [DPSY01-
CTRAHMI] to SBO when operation from the IED front panel is required, we discuss how to set
User interface: Control sub-menu
this in chapter
Failed
Select
Select logic
decision
- 675 -
Signal output
Success
.
6F2S1914 (0.49)
Control
.
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading