Toshiba GR200 Series Instruction Manual page 770

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Cancel logic for SBO mode
4.3.3
In the SBO control mode, the reception of a cancel command is possible; when the cancel
conditions are satisfied, accordingly, the function can discard the select command.
Receiving "Cancel" from remote-end
(i)
Figure 4.3-13 shows the logic when a "Cancel command (Remote-Cancel)" signal is applied to
the SOFTSW1 function. The input-point "S4301_CONTROL_REQ" is the same as the
"Selection command (Remote-On-Control)" signal.
Input
Command "Remote-cancel"
522001 700A046D08
S4301_CONTROL_REQ
Figure 4.3-13 Cancel logic by the reception of the command from the remote end
†Note: The criteria "unmatched conditions" are determined when the "Test-bit status" in
the 'cancel' command is not identical to the "IED test status".
Receiving "Cancel" from local-end
(ii)
Figure 4.3-14 shows the logic when a "Cancel command (Local-cancel)" signal is applied to the
SOFTSW1 function. The input signal is provided when the "Cancel" key is pressed on the IED
front panel; the user is not required to map it. When the logic receives input "Local-cancel"
signal, the logic is able to output a result signal, provided that the "unmatched condition
detected" checking is satisfied.
Input
Command "Local-cancel"
Figure 4.3-14 Cancel logic by the reception of the command at local end
†Note: The criteria "unmatched conditions" are determined when the "Test-bit status" in
the 'cancel' command is not identical to the "IED test status".
Operate logic for SBO/DIR modes
4.3.4
The user should map the operation command to the operate logic. If the operation conditions
are satisfied, the IED is able to change the state in the SOFWSW1–61 (S43-01 to S43-61).
510001 7001016D08
Cancel logic in SOFTSW1
SOFTSW1 function (Function ID: 522001)
Cancel command
Unmatched condition
detected†
510001 7001016D08
Cancel logic in SOFTSW1
SOFTSW1 function (Function ID: 522001)
Cancel command
Unmatched condition
detected†
- 747 -
6F2S1914 (0.49)
Output
Successes to cancel
&
Operation Failed
&
Output
Successes to cancel
&
&
Operation Failed
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading