Toshiba GR200 Series Instruction Manual page 737

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Signals from the
BI circuit and DPSY01
devices
Single phase signals
BI signal selected by
setting [DPSY01A-NOPSG]
N/O contact
signal
BI signal selected by
setting [DPSY01A-NCLSG]
N/C contact
signal
[DPSY01-EN]
[DPSY01-DEVTYPE]
Figure 4.2-41 Acquisition of single-phase signal at DPSY01
‡Note: In Figure 4.2-41 two signals can be issued "DPSY01_3PH_STATE" and
"DPSY01_F_QLT_SPP", which are the same as the signals in the Figure 4.2-40.
Event suppression
If the status of a device "chatters" for a short time, the DPSY function will receive iterative
signals from the device. Such iterative signals can cause extra burden for the DPSY function;
hence, event suppression can be required to reduce the additional burden created.
2
Signal
from device
1
3
Suppressed
signal
A
Time.................
Figure 4.2-42 Iterative signals and signals suppressed
Figure 4.2-42 shows that the iterative signals received from the device have been
suppressed by the event suppression function. The suppression commences on receipt of the
seventh signal (at Time 'B'). This is because the function can count the iterative number of
incoming signals. Detection commences at Time 'A', the setting [DPSY-NELD] is provided so
that the suppression commences at Time B. The setting [DPSY-TELD] is pertains to the
DPSY01
&
&
&
On
1-Pole
[DPSY-NELD]
4
6
8
5
7
[DPSY-TELD]
B
- 714 -
Signal acquisition logic in DPSY01
&
1≥
Open
&
Faulty
&
Intermediate
&
Close
C
6F2S1914 (0.49)
Output ‡
To select and operate
condition logics
"DPSY01_3PH_STATE"
(511001 3102011001)
Event
Suppression
detector
"DPSY01_ F_QLT_SPP"
(511001 8102011F5F)
[DPSY-TELR]
E
D
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading

Table of Contents