Functions, monitoring, and protective functions
9.3 Extended functions
9.3.4

Extended monitoring functions

Description
The "extended monitoring functions" function module enables additional monitoring
functions:
● Speed setpoint monitoring: |n_set| ≤ p2161
● Speed setpoint monitoring: n_set > 0
● Load monitoring
Description of load monitoring
This function monitors power transmission between the motor and the working machine.
Typical applications include V-belts, flat belts, or chains that loop around the belt pulleys or
cog wheels of drive and outgoing shafts and transfer the peripheral speeds and forces. Load
monitoring can be used here to identify blockages in the working machine and interruptions
to the power transmission.
For load monitoring, the current speed/torque curve is compared with the programmed
speed/torque curve (p2182 to p2190). If the current value is outside the programmed
tolerance bandwidth, a fault or alarm is triggered depending on parameter p2181. The fault
or alarm message can be delayed by means of parameter p2192 to prevent false alarms
caused by brief transitional states.
Figure 9-20
566
Load monitoring (p2181 =1)
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A