Functions, monitoring, and protective functions
9.2 Drive functions
Notes
When quick magnetization is selected (p1401.6 = 1), smooth starting is deactivated internally
and alarm A07416 displayed.
When the stator resistance identification function is active (see p0621 "Identification of stator
resistance after restart"), quick magnetization is deactivated internally and alarm A07416
displayed.
The parameter does not work when combined with the "flying restart" function (see p1200),
i.e. flying restart is performed without quick magnetization.
Function diagram
FP 6491
FP 6722
FP 6723
Parameter
• p0320
• p0346
• p0621
• p0640
• p0644
• p1401
• p1570
• p1573
• p1590
• p1616
486
Flux control configuration
Field weakening characteristic, Id setpoint (ASM, p0300 = 1)
Field weakening controller, flux controller (ASM, p0300 = 1)
Motor rated magnetization current / short-circuit current
Motor excitation build-up time
Stator resistance identification after restart
Current limit
Induction motor excitation current limit
Flux control configuration
Flux setpoint
Flux threshold value magnetization
Flux controller P gain
Current setpoint smoothing time
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A