Functions, monitoring, and protective functions
9.3 Extended functions
Parameterization
Once the bypass without synchronization (p1260 = 3) function has been activated, the
following parameters must be set.
Table 9- 9
Parameters
r1261.0
r1261.1
p1262 =
p1263 =
p1264 =
p1265 =
p1266 =
p1267.0 =
p1267.1 =
p1269[0] =
p1269[1] =
p3800 = 0
P1200 = 1
9.3.2.4
Function diagram
FP 7020
9.3.2.5
Parameters
Bypass function
• p1200
• p1260
• r1261
• p1262
• p1263
• p1264
• p1265
• p1266
• p1267
• p1268
• p1269
• p1274
560
Parameter settings for bypass function with synchronizer without degree of overlapping
Signal "Command switch motor - power unit"
Signal "Command switch motor - line supply"
Bypass dead time setting
Debypass delay time setting
Bypass delay time setting
Speed threshold setting when p1267.1 = 1
Control signal setting when p1267.0 = 1
Trigger signal setting for bypass function
Signal source to provide the feedback signal of contactor K1
Signal source for contactor K2 feedback
Synchronization is deactivated.
The "flying restart" function is always active.
Synchronization
Flying restart operating mode
Bypass configuration
CO/BO: Bypass control/status word
Bypass dead time
Debypass delay time
Bypass delay time
Bypass speed threshold
BI: Bypass control command
Bypass changeover source configuration
BI: Bypass feedback signal synchronization completed
BI: Bypass switch feedback signal
BI: Bypass switch monitoring time
Description
Operating Instructions, 07/2016, A5E03347396A
Converter cabinet units