Electrical installation
4.10 Other connections
NOTICE
Damage to the dv/dt filter if it is not activated during commissioning
The dv/dt filter may be damaged if it is not activated during commissioning.
• Activate the dv/dt filter during commissioning using parameter p0230 = 2.
NOTICE
Damage to the dv/dt filter if a motor is not connected
dv/dt filters which are operated without a motor being connected can be damaged or
destroyed.
• Never operate a dv/dt filter connected to the Power Module without a connected motor.
Note
Setting pulse frequencies
It is permissible to set pulse frequencies in the range between the rated pulse frequency and
the maximum pulse frequency when a dv/dt filter plus Voltage Peak Limiter is used. When so
doing, take into account the "Current derating as a function of the pulse frequency; see
Technical data.
Commissioning
During commissioning, the dv/dt filter plus Voltage Peak Limiter must be logged on using
STARTER or the AOP30 operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.
122
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A