Siemens SINAMICS G150 Operating Instructions Manual page 222

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Commissioning
5.3 Procedure for commissioning with STARTER
⇒ To select a different predefined encoder configuration, check the Select standard encoder
from list radio button and select one of the encoders from the list.
⇒ To enter special encoder configurations, click the Enter data radio button and then the
Encoder data button. The following input screen is displayed for you to enter the required
data.
Figure 5-25
Entering encoder data – User-defined encoder data
⇒ Select the measuring system.
In conjunction with SINAMICS G150, the following encoders can be selected:
● HTL
● TTL
⇒ Enter the required encoder data.
⇒ Under the Details tab, special encoder properties can be set, for example, gear ratio, fine
resolution, inversion, measuring gear position tracking.
⇒ Click OK.
222
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A