Synchronization - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

9.2.18

Synchronization

Description
The "Synchronization" function and an existing VSM10 Voltage Sensing Module (to measure
the line voltage) synchronizes a motor to the line supply. The connection to the line supply or
the required contactor activation can be made via the available bypass function or via a
higher-level control system.
The use of the bypass function permits the temporary (e.g. to perform maintenance work
without system standstill) or permanent operation of the motor on the line supply.
The p3800 parameter activates the synchronization. The voltage is acquired via a VSM10
assigned to the drive (via DRIVE-CLiQ) and measures the line supply voltage.
Features
● Connector inputs for the actual voltage sensing of the motor via VSM10 (p3661, r3662)
● Setting a phase difference (p3809)
● Can be activated by parameter (p3800)
● Enable via parameter (p3802)
Function diagram
FP 7020
Parameter
• p3800[0...n]
• p3801[0...n]
• p3802[0...n]
• r3803
• r3804
• r3805
• p3806[0...n]
• r3808
• p3809[0...n]
• p3811[0...n]
• r3812
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Technology functions - Synchronizing
Sync network drive activation
Sync-line-drive drive object number
BI: Sync network drive enable
CO/BO: Sync network drive control word
CO: Sync network drive target frequency
CO: Sync network drive frequency difference
Sync network drive frequency difference threshold value
CO: Sync network drive phase difference
Sync network drive phase setpoint value
Sync network drive frequency limitation
CO: Sync network drive correction frequency
Functions, monitoring, and protective functions
9.2 Drive functions
525

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents