6.6.5

Menu commissioning / service

6.6.5.1
Drive commissioning
This option enables you to re-commission the drive from the main menu.
Basic commissioning
Only the basic commissioning parameters are queried and stored permanently.
Complete commissioning
Complete commissioning with motor and encoder data entry is carried out. Following this,
key motor parameters are recalculated from the motor data. The parameter values
calculated during previous commissioning are lost.
In a subsequent motor identification procedure, the calculated values are overwritten.
Motor identification
The selection screen for motor identification appears.
Reset fan operating time
The actual operating hours of the fan in the power unit is displayed.
After a fan replacement, the operating hours counter for monitoring the fan operating time
must be reset.
6.6.5.2
Device commissioning
Device commissioning
In this menu, you can enter the device commissioning status directly. This is the only way
that you can reset parameters to the factory setting for example.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
6.6 Control via the operator panel
Operation
295