Siemens SINAMICS G150 Operating Instructions Manual page 227

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Selecting process data exchange
Figure 5-28
⇒ Select the PROFIdrive telegram type.
Message frame types
● 1: Standard telegram 1, PZD-2/2
● 2: Standard telegram 2, PZD-4/4
● 3: Standard telegram 3, PZD-5/9
● 4: Standard telegram 4, PZD-6/14
● 20: SIEMENS telegram 20, PZD-2/6
● 220: SIEMENS telegram 220, PZD-10/10
● 352: SIEMENS telegram 352, PZD-6/6
● 999: Free telegram configuration with BICO (default setting)
⇒ Click Continue >
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Selecting process data exchange
5.3 Procedure for commissioning with STARTER
Commissioning
227