Connecting - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 1750 kw 2700 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

4.10.17.2

Connecting

Temperature sensor connections
Table 4- 48
X531-X536 temperature sensor inputs
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm
Measuring current via temperature sensor connection: approx. 0.83 mA
When connecting temperature sensors with 3 wires, a jumper must be inserted between
X53x.2 and X53x.4.
Table 4- 49
Terminal
X531
X532
X533
X534
X535
X536
Danger to life due to electric shock in the event of voltage flashovers at the temperature
sensor
Voltage flashovers in the signal electronics can occur in motors without safe electrical
separation of the temperature sensors.
• Use temperature sensors that fully comply with the specifications of the safety isolation.
Converter cabinet units
Operating Instructions, 07/2016, A5E03347396A
Function
Function
1x2-/2x2-wire
3 and 4-wire
+Temp
+
(channel x)
(Channel x)
-Temp
-
(channel x)
(Channel x)
+Temp
+ I
c
(channel y)
(constant current,
positive channel x)
-Temp
- I
c
(channel y)
(constant current,
negative channel x)
2
Channel assignment
Channel number [x]
for 1x2, 3 and 4-wires
0
1
2
3
4
5
WARNING
4.10 Other connections
Technical data
Temperature sensor connection for sensors with
1x2 wires
Connection of the 2nd measuring cable for sen-
sors with 4 wires
Temperature sensor connection for sensors with
1x2 wires
Connection of the 1st measuring cable for sen-
sors with 3 and 4 wires.
Temperature sensor connection for sensors with
2x2, 3 and 4-wires
Channel number [y]
for 2x2 wires
6
7
8
9
10
11
Electrical installation
151