Tm54F: Internal Hardware Error - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

bb = 0A hex: p10023
bb = 0B hex: p10024
bb = 0C hex: p10025
bb = 0D hex: p10026
bb = 0E hex: p10027
bb = 0F hex: p10028
bb = 10 hex: p10036
bb = 11 hex: p10037
bb = 12 hex: p10038
bb = 13 hex: p10039
bb = 14 hex: p10040
bb = 15 hex: p10041
bb = 16 hex: p10042
bb = 17 hex: p10043
bb = 18 hex: p10044
bb = 19 hex: p10045
bb = 1A hex: p10046
bb = 1B hex: Test stop internal p10041
bb = 1C hex: Test stop internal p10046
bb = 1D hex: - 1F hex test stop internal p10017, p10002, p10000
bb = 20 hex: - 2A hex test stop internal p10040
bb = 2B hex: Test stop initialization
bb = 2C hex: Input/output calculation initialization
bb = 2D hex: - 45 hex internal data for output calculation, P10042 - P10045
bb = 46 hex - 63 hex data for SGE calculation of drive group 1
bb = 64 hex - 81 hex data for SGE calculation of drive group 2
bb = 82 hex - 9F hex data for SGE calculation of drive group 3
bb = A0 hex - BD hex data for SGE calculation of drive group 4
bb = BE hex debounce time of FDI inputs, P10017
bb = BF hex debounce time of DI inputs, P10017
bb = C0 hex debounce time of diag inputs, P10017
cc: Index of the data to be cross-checked that resulted in the error.
Remedy:
Carry out the following steps on the TM54F:
- activate the safety commissioning mode (p0010 = 95).
- start the copy function for SI parameters (p9700 = 57 hex).
- acknowledge complete data change (p9701 = AC hex).
- exit the safety commissioning mode (p0010 = 0).
- save all parameters (p0977 = 1).
- carry out safe acknowledgement (p10006).
For an internal software error (aaaa greater than zero):
- upgrade the software on the TM54F.
- contact the Hotline.
- replace the TM54F.
235052
<location>TM54F: Internal hardware error
Message value:
%1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM54F_MA, TM54F_SL
Reaction:
NONE
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
An internal software/hardware error has been detected on the Terminal Module 54F (TM54F).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the electrical cabinet design and cable routing for EMC compliance
- upgrade TM54F firmware to more recent version.
- contact the Hotline.
- replace the TM54F.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
851