Si Cu: No Automatic Firmware Update; Si Cu: System Is Defective - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

201664
<location>SI CU: No automatic firmware update
Message value:
%1
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
During booting, the system detected that the "Firmware update automatic" function (p7826 = 1) was not activated. This
function must be activated for automatic firmware updates/downgrades to prevent impermissible version combinations
when safety functions are enabled.
Note:
This fault does not result in a safety stop response.
See also: p7826 (Firmware update automatic)
Remedy:
For enabled drive-based SI monitoring:
1. Activate the "Firmware update automatic" function (p7826 = 1).
2. Save the parameters (p0977 = 1) and carry out a POWER ON.
When de-activating drive-based SI monitoring (p9601 = 0), the fault can be acknowledged after exiting the safety com-
missioning mode.
201665
<location>SI CU: System is defective
Message value:
%1
Drive object:
SERVO_COMBI, SERVO_SINUMERIK828
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
Before the drive booted the last time, it detected a defect in the system and carried out an emergency stop.
Fault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
Remedy:
- carry out a POWER ON (power off/on).
- upgrade firmware to later version.
- contact the Hotline.
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
569