Infeed: Supply Voltage (P0210) Incorrect; Master/Slave: 4-Channel Multiplexer Control Not Valid; Master/Slave: 6-Channel Multiplexer Control Not Valid - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

SINAMICS alarms
206311
<location>Infeed: Supply voltage (p0210) incorrect
Message value:
Line supply voltage: %1
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, SIC_COMBI, SIC_SINUMERIK_828
Reaction:
OFF2 (OFF1)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The line voltage nominal value indicated in p0210 is outside the nominal voltage range of the power unit.
After pre-charging was completed, the current line supply voltage Vrms was calculated using the measured DC link
voltage. This voltage Vrms does not lie within the extended tolerance range of the supply voltage set in p0210.
The following applies for the extended tolerance range: 75 % * p0210 < Vrms < 120 % * p0210
Alarm value (r2124, floating point):
Line supply voltage Vrms present.
See also: p0210 (Drive unit line supply voltage)
Remedy:
- check the parameterized supply voltage and if required change (p0210).
- check the line supply voltage.
See also: p0210 (Drive unit line supply voltage)
206320
<location>Master/slave: 4-channel multiplexer control not valid
Message value:
%1
Drive object:
AFE_SINUMERIK_828
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Values 0, 1, 2, and 3 are valid to control the 4-channel multiplexer via connector input 3572.
In this case, an invalid value was identified. The control remains effective with the previous value.
Fault value (r0949, interpret decimal):
Invalid value to control the multiplexer.
See also: p3572 (Master/slave active current setpoint, multiplexer selection)
Remedy:
- check the interconnection to control the multiplexer (CI: p3572).
- check the signal source signal value of the BICO interconnection.
See also: p3572 (Master/slave active current setpoint, multiplexer selection)
206321
<location>Master/slave: 6-channel multiplexer control not valid
Message value:
%1
Drive object:
AFE_SINUMERIK_828
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Values 0, 1, 2, 3, 4 and 5 are valid to control the 6-channel multiplexer via CI: 3577. In this case, an invalid value was
identified. The control remains effective with the previous value.
Fault value (r0949, interpret decimal):
Invalid value to control the multiplexer.
See also: p3577 (Master/slave current distribution factor, multiplexer selection)
Remedy:
- check the interconnection to control the multiplexer (CI: p3577).
- check the signal source signal value of the BICO interconnection.
See also: p3577 (Master/slave current distribution factor, multiplexer selection)
628
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinumerik 828d

Table of Contents