Cu Drive-Cliq (Cu): Cyclic Data Transfer Error; Pu Drive-Cliq (Cu): Error When Sending Drive-Cliq Data; Power Unit Drive-Cliq (Cu): Component Fault - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

230885
<location>CU DRIVE-CLiQ (CU): Cyclic data transfer error
Message value:
Component number: %1, fault cause: %2
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, CU_LINK, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the power unit to the Control Unit involved.
The nodes do not send and receive in synchronism.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 1A hex = 26 dec:
Sign-of-life bit in the receive telegram not set and the receive telegram is too early.
xx = 21 hex = 33 dec:
The cyclic telegram has not been received.
xx = 22 hex = 34 dec:
Timeout in the telegram receive list.
xx = 40 hex = 64 dec:
Timeout in the telegram send list.
xx = 62 hex = 98 dec:
Error at the transition to cyclic operation.
Remedy:
- check the power supply voltage of the component involved.
- carry out a POWER ON.
- replace the component involved.
See also: p9915 (DRIVE-CLiQ data transfer error shutdown threshold master)
230886
<location>PU DRIVE-CLiQ (CU): Error when sending DRIVE-CLiQ data
Message value:
Component number: %1, fault cause: %2
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, CU_LINK, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
A DRIVE-CLiQ communication error has occurred from the power unit to the Control Unit involved.
Data were not able to be sent.
Fault value (r0949, interpret hexadecimal):
yyxx hex: yy = component number, xx = fault cause
xx = 41 hex:
Telegram type does not match send list.
Remedy:
Carry out a POWER ON.
230887
<location>Power unit DRIVE-CLiQ (CU): Component fault
Message value:
Component number: %1, fault cause: %2
Drive object:
AFE_SINUMERIK_828, BIC_SINUMERIK_828, CU_LINK, SERVO_COMBI, SERVO_SINUMERIK828, SIC_COMBI,
SIC_SINUMERIK_828, TM120
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
733

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinumerik 828d

Table of Contents