Topology: Comparison Endat Encoder Missing In The Actual Topology; Comparison Motor With Drive-Cliq Missing In The Actual Topology - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Remedy:
- delete the option board in the commissioning software project and download the new configuration to the drive unit.
- re-configure the drive unit in the commissioning software project and download the new configuration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check that the option board is functioning correctly
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
201488
<location>Topology: Comparison EnDat encoder missing in the actual topology
Message value:
Component number: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected an EnDat encoder in the target topology that is not available in the actual topol-
ogy.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy:
- re-configure the drive belonging to the encoder in the commissioning software project (encoder configuration) and
download the new configuration to the drive unit.
- delete the drive belonging to the encoder in the commissioning software project and download the new configuration
to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
201489
<location>Topology: Comparison motor with DRIVE-CLiQ missing in the actual
topology
Message value:
Component number: %1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The topology comparison has detected a motor with DRIVE-CLiQ in the target topology that is not available in the
actual topology.
Alarm value (r2124, interpret decimal):
Component number of the additional target components.
Remedy:
- re-configure the drive belonging to this motor in the commissioning software project and download the new configu-
ration to the drive unit.
- re-configure the drive belonging to this motor in the commissioning software project and download the new configu-
ration to the drive unit.
- check that the actual topology matches the target topology and if required, change over.
- check DRIVE-CLiQ cables for interruption and contact problems.
- check that the motor is working properly.
Note:
Under "Topology --> Topology view" the commissioning software offers improved diagnostics capability (e.g. setpoint/
actual value comparison).
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms
553