Siemens SINAMICS G120 Operating Instructions Manual page 75

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Frame sizes FSD ... FSF
Table 4-14
Frame
size
FSD
FSE
FSF
BOP-2, IOP-2 or blanking cover
1)
Power Module depth without Control Unit: FSD, FSE 237 mm, FSF 357 mm
2)
Table 4-15
Frame
size
FSD
FSE
FSF
The Power Module is designed for mounting without any lateral cooling air clearance. For tolerance
1)
reasons, we recommend a lateral clearance of approx. 1 mm.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Dimensions depend on the operator panel (OP) that is inserted
Width
Height [mm]
[mm]
without shield
plate
275
517
354
615
384
754
Drilling dimensions, cooling clearances and fixing
Drilling dimensions [mm]
h
b
c
430
170
7
509
230
8.5
680
270
13
Mounting depth in the cabinet with
with shield plate
without OP
650
722
1021
Cooling air clearances [mm]
Top
Bottom
Front
300
350
300
350
300
350
Installing
4.3 Installing Power Modules
1)
Control Unit (CU) [mm]
2)
with OP
253
264
253
264
373
384
Fixing/torque [Nm]
1)
100
4 x M5 / 6.0
100
4 x M6 / 10
100
4 x M8 / 25
1)
75

Hide quick links: