6.9 Drive control via BACnet MS/TP
Bit
2
3
4
5
6
7
8, 9
10
11
12
13
14
15
242
Meaning
0 = Quick stop (OFF3)
1 = No quick stop (OFF3) The motor can be switched on (ON
0 = Inhibit operation
1 = Enable operation
0 = Disable RFG
1 = Do not disable RFG
0 = Stop RFG
1 = Enable RFG
0 = Inhibit setpoint
1 = Enable setpoint
0 → 1 = Acknowledge
faults
Reserved
0 = No control via PLC
1 = Control via PLC
1 = Direction reversal
Reserved
1 = MOP up
1 = MOP down
Reserved
Explanation
Quick stop: The motor brakes with the
OFF3 ramp-down time p1135 down to
standstill.
command).
Immediately switch-off motor (cancel
pulses).
Switch-on motor (pulses can be ena‐
bled).
The inverter immediately sets its ramp-
function generator output to 0.
The ramp-function generator can be
enabled.
The output of the ramp-function gener‐
ator stops at the actual value.
The output of the ramp-function gener‐
ator follows the setpoint.
The inverter brakes the motor with the
ramp-down time p1121 of the ramp-
function generator.
Motor accelerates with the ramp-up
time p1120 to the setpoint.
Acknowledge fault. If the ON com‐
mand is still active, the inverter
switches to "closing lockout" state.
Inverter ignores the process data from
the fieldbus.
Control via fieldbus, inverter accepts
the process data from the fieldbus.
Invert setpoint in the inverter.
Increase the setpoint saved in the mo‐
torized potentiometer.
Reduce the setpoint saved in the mo‐
torized potentiometer.
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
BACNet
Signal inter‐
connection in
the inverter
BV28
p0848[0] =
r2090.2
BV26
p0852[0] =
r2090.3
BV26
p1140[0] =
r2090.4
BV26
p1141[0] =
r2090.5
BV26
p1142[0] =
r2090.6
BV22
p2103[0] =
r2090.7
N/A
---
BV93
p0854[0] =
r2090.10
BV21
p1113[0] =
r2090.11
N/A
---
N/A
p1035[0] =
r2090.13
N/A
p1036[0] =
r2090.14
N/A
---
Converter with the CU230P-2 Control Units