Technical data
10.5 Technical data, PM330 Power Module
10.5.2

Power-dependent technical data, PM330

Note
Recommended connection cross-sections
The recommended connection cross-sections are determined for copper cables at 45 °C
ambient temperature and cables with a permitted operating temperature at the conductor of
70 °C (routing type C - factor for bundling 0.75 considered) according to DIN VDE
0298-4/08.03).
Protective conductor cross-section (S: Cross-section of the supply connection phase
conductor, MS: Cross-section of the external protective conductor):
Minimum cross-sections:
● S < 16 mm² → MS = S
● 16 mm² ≤ S ≤ 35 mm² → MS = 16 mm²
● S > 35 mm² → MS = 0.5 × S
Recommended cross-sections:
● MS ≥ S
Table 10-30 PM330 frame sizes GX, 3-phase 380 ... 480 VAC
Article No.
Rated input current
- at 380/400 V, 45° C
- at 480 V, 45° C
- at 380/400 V, 55° C
- at 480 V, 55° C
Rated input current DCP/DCN
(for 2/3 of the inverter power)
- at 510 V
, 45 °C
DC
- at 650 V
, 45 °C
DC
- at 510 V
, 55 °C
DC
- at 650 V
, 55 °C
DC
Rated output current I
N
- at 380/400 V, 45° C
- at 480 V, 45° C
- at 380/400 V, 55° C
- at 480 V, 55° C
LO base load power
LO base load input current at 400 V
LO base load output current at 400 V
HO base load power
HO base load input current at 400 V
HO base load output current at 400 V
466
6SL3310-
1PE33-0AA0
317 A
262 A
269 A
220 A
255 A
209 A
217 A
177 A
300 A
245 A
255 A
208 A
160 kW
307 A
290 A
132 kW
254 A
240 A
1PE33-7AA0
375 A
314 A
319 A
266 A
315 A
263 A
268 A
223 A
370 A
308 A
315 A
262 A
200 kW
365 A
360 A
160 kW
300 A
296 A
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
1PE34-6AA0
469 A
376 A
399 A
319 A
392 A
314 A
333 A
267 A
460 A
369 A
391 A
313 A
250 kW
459 A
450 A
200 kW
375 A
368 A