Technical data
10.4 Technical Data, PM240P-2 Power Module
Article number without filter
Article number with filter
HO base load input current
HO base load output current
Siemens fuse according to IEC/UL
Fuse according to IEC/UL, Class J
Power loss without filter
Power loss with filter
Required cooling air flow
Weight without filter
Weight with filter
462
6SL3210-1RH31-4UL0
6SL3210-1RH31-4AL0
122 A
115 A
3NE1225-0 / 200 A
200 A
2.56 kW
2.59 kW
153 l/s
60 kg
64 kg
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE