Technical data
10.5 Technical data, PM330 Power Module
10.5
Technical data, PM330 Power Module
Permissible inverter overload
The inverters have different load capabilities, "High Overload" and "Low Overload", depending
on the expected.
Figure 10-4
10.5.1
General technical data, PM330
Table 10-29 General technical data
Electrical data
Line system configurations
Line requirement
Line voltage
Line frequency
Output frequency
Displacement factor cos φ
power factor λ
Converter efficiency
Short-circuit current rating ac‐
cording to IEC, in conjunction
with the specified fuses
Short-circuit current rating ac‐
cording to UL61800-5-1 (up
to 480 V AC or 600 V AC), in
conjunction with the specified
fuses
Overvoltage category
Mechanical data
Degree of protection
Protection class
Cooling method
Sound pressure level L
PA
ma)
464
Load cycles, Low Overload" and "High Overload"
Grounded TN/TT systems or ungrounded IT systems (a grounded phase conductor is not
permissible in 690 V line supplies)
A line reactor (2% u
k
380 V (-10 %) ... 480 V (+10 %)
500 V (-10 %) ... 690 V (+10 %)
47 ... 63 Hz
0 ... 100 Hz
0.96
0.75 ... 0.93 (with line reactor u
> 98%
160 ... 630 kW: 100 kA
160 ... 630 kW: 100 kA
Can be used on line supplies that cannot supply more than 100 kA symmetrically at a maxi‐
mum voltage of 480 V AC or 600 V AC when they are protected with the semiconductor fuses
specified in Chapter "Technical Data" of this manual.
III according to EN 61800-5-1
IP20
according to EN 61800-5-1: Class I (with protective conductor system) and Class III (PELV)
Forced air cooling AF according to EN 60146
(1
≤ 74 dB(A)
1)
) must be connected in series
= 2%)
k
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Converter with the CU230P-2 Control Units