Siemens SINAMICS G120 Operating Instructions Manual page 286

Low voltage converters built-in and wall mounting units with cu230p-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.20 Multi-zone control
Example
In an open plan office, temperature sensors (Lg-Ni1000) are installed in three different places.
The inverter receives the measured values and temperature setpoint via its analog inputs.
Temperature setpoints between 8° C ... 30° C are permissible. Overnight, the average
temperature should be 16° C.
Parameter
p2200[0] = 1
p2251 = 0
p2900[0] = 16
p31020 = 1
p31021 = 0
p31022 = 7
p31023[0] = 755[0]
p0756[0] = 0
p0757[0] = 0
p0758[0] = 8
p0759[0] = 10
p0760[0] = 30
p31023[1] = 2900
p31026[0]= 755.2
p0756[2] = 6
p0757[2] = 0
p0758[2] = 0
p31023[1] = 2900
p31026[0]= 755.2
p0756[2] = 6
p0757[2] = 0
p0758[2] = 0
p0759[2] = 100
p0760[2] = 100
p31026[1] = 755[3]
p0756[3] = 6
p0757[3] = 0
p0758[3] = 0
p0759[3] = 100
p0760[3] = 100
p31026[2] = 755[1]
p0756[1] = 2
p0757[1] = 0
p0758[1] = 0
286
Description
Technology controller enable
Technology closed-loop controller as main setpoint
Temperature setpoint overnight as a fixed percentage value
Activate multi-zone control
Multi-zone control with one setpoint and three actual values
Three actual values, one setpoint. The actual value of the closed-loop control is
the average value of three actual values.
Temperature setpoint via analog input AI 0
Select analog input type (voltage input 0 ... 10 V)
Lower value = 8° C (0 V ≙ 8° C)
Upper value = 30° C (10 V ≙ 30° C)
Interconnect p31023[1] with the value from p2900 for the reduction overnight
Temperature actual value 1 via analog input 2 as a percentage value
Analog input type (temperature sensor LG-Ni1000)
Lower value of the scaling characteristic
Interconnect p31023[1] with the value from p2900 for the reduction overnight
Temperature actual value 1 via analog input 2 as a percentage value
Analog input type (temperature sensor LG-Ni1000)
Lower value of the scaling characteristic
Upper value of the scaling characteristic
Temperature actual value 2 via analog input AI 3 in %
Select analog input type (temperature sensor LG-Ni1000)
Lower value of the scaling characteristic
Upper value of the scaling characteristic
Temperature actual value 3 via a temperature sensor with current output
(0 mA ... 20 mA) via analog input AI 1
Analog input type (current input 0 ... 20 mA)
Lower value of the scaling characteristic (0 mA ≙ 0° C)
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE