Advertisement

Commissioning
5.3 Preparing for commissioning
You have formed the DC link.
Parameter
Parameter
p0010
p3380
r3381
r3382
Form DC Link of the PM240‑2 power module
You form the DC-link capacitors by supplying a line voltage of ≤100 V to the inverter for a
defined time.
Figure 5-3
Form DC Link of other power modules
Formation of the DC link capacitors is not required for the following power modules even after
a lengthy period of storage.
● PM230
● PM240P‑2
● PM250
150
Description
Drive commissioning parameter filter (factory setting: 0)
0: Ready
2: Power unit commissioning
DC link forming, forming duration (factory setting: 0 h)
p3380 = 0 deactivates the function.
If the forming duration is changed while forming, then forming restarts with the modified
forming duration.
DC link forming, remaining time [h]
Remaining forming time.
DC link forming, status word
.00
1 signal: Forming activated
.01
1 signal: Forming active
.02
1 signal: Forming completed
.03
1 signal: Forming faulty
The inverter signals fault F07390
Forming the DC-link capacitors
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE