Number
Cause
F30022
Power Module: Monitoring U
F30027
Time monitoring for DC link pre-
charging
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30052
Incorrect Power Module data
F30053
Error in FPGA data
F30059
Internal fan defective
F30074
Communications error between
Control Unit and Power Module
A30502
DC-link overvoltage
F30662
CU hardware fault
F30664
CU power up aborted
F30850
Software fault in the Power Module Replace Power Module or contact technical support.
A30920
Temperature sensor fault
A50001
PROFINET configuration error
A50010
PROFINET name of station invalid
A50020
PROFINET: Second control missing "Shared Device" is activated (p8929 = 2). However, only the connection to
For further information, please refer to the List Manual.
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Remedy
Check or replace Power Module.
CE
Check the line voltage at the input terminals.
Check the line voltage setting (p0210).
● Check whether the fan is running.
● Check the fan filter elements.
● Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
● Check the motor load.
● Check the line phases
Check the internal fan and if required replace.
Replace the Power Module or upgrade the Control Unit firmware.
Replace the Power Module.
Check the internal fan and if required replace.
There is a communications fault between the Control Unit and the Power
Module. Possible causes:
● The Control Unit may have been removed or inserted incorrectly.
● The external 24 V Control Unit power supply has dipped to ≤95% of the
rated voltage for ≤3 ms
● Check the device supply voltage (p0210).
● Check the line reactor dimensioning
Switch the Control Unit off and on again, upgrade the firmware or contact
technical support.
Switch the Control Unit off and on again, upgrade the firmware or contact
technical support.
Check that the sensor is connected correctly.
A PROFINET control is attempting to establish a connection with an incor‐
rect configuration telegram. Check whether "Shared Device" is activated
(p8929 = 2).
Correct the name of station (p8920) and activate (p8925 = 2).
a PROFINET control is available.
Overview of the manuals (Page 537)
Alarms, faults and system messages
8.6 List of alarms and faults
413