6.17.2
Invert setpoint
The inverter provides an option to invert the setpoint sign using a bit. As an example, the
setpoint inversion is shown through a digital input.
To invert the setpoint via an external signal, interconnect parameter p1113 with a binary signal,
e.g. digital input 1.
Table 6-38
Parameter Remark
p1113
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE
Application example for inverting the setpoint
Setpoint inversion (factory setting depends on the inverter)
p1113 = 722.1
Digital input 1 = 0: Setpoint remains unchanged.
Digital input 1 = 1: Inverter inverts the setpoint.
p1113 = 2090.11
Invert setpoint via control word 1, bit 11.
Advanced commissioning
6.17 Setpoint calculation
267