Alarms, faults and system messages
8.5 Faults, alarm buffer and alarm history
Parameter
p2126[0 ... 19]
p2127[0 ... 19]
You will find details in function diagram 8075 and in the parameter description of the List
Manual.
406
Description
Setting the fault number for the acknowledgement mode
Selection of the faults for which the acknowledgement type should be changed.
You can modify the acknowledgement type for up to 20 different fault codes.
Setting, acknowledgement mode
Setting the acknowledgement type for the selected fault
1: Acknowledgement only using POWER ON
2: IMMEDIATE acknowledgement after removing the fault cause
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE