Alarms, faults and system messages

8.2 System runtime

8.2
System runtime
By evaluating the system runtime of the inverter, you can decide when you should replace
components subject to wear in time before they fail - such as fans, motors and gear units.
Principle of operation
The system runtime is started as soon as the Control Unit power supply is switched-on. The
system runtime stops when the Control Unit is switched off.
The system runtime comprises r2114[0] (milliseconds) and r2114[1] (days):
System runtime = r2114[1] × days + r2114[0] × milliseconds
If r2114[0] has reached a value of 86,400,000 ms (24 hours), r2114[0] is set to the value 0 and
the value of r2114[1] is increased by 1.
Parameter
r2114[0]
r2114[1]
You cannot reset the system runtime.