Toshiba GR200 Series Instruction Manual page 985

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Measurement of operation Intervals
4.9.5
The TPOS01 function can measure operation intervals time†, the intervals OT1 and OT2 can
represent the period of time when an earth-switch changes a position from another position.
As shown in Table 4.9-27 the eight intervals are defined as switching as shown in Figure 4.9-50
to Figure 4.9-53. The user should set scheme switch [TPOS01-OPETMEN] On.
Signal "TPOS01_P2EX_BO"
Sensing intermediate state
P1
P2
P3
P2-control
a. Switch motion (P1 to P2)
Figure 4.9-50 Two Intervals (OT1 and OT2) for P2 control
Signal "TPOS01_P1EX_BO"
P1
P2
P3
P1-control
a. Switch motion (P2 to P1)
Figure 4.9-51 Two Intervals (OT3 and OT4) for P1 control
Signal "TPOS01_P2EX_BO"
P1
P2
P3
P2-control
a. Switch motion (P3 to P2)
Figure 4.9-52 Two Intervals (OP5 and OP6) for P2 control
Signal "TPOS01_PT_P1"
Signal "TPOS01_PT_P2"
Signal "TPOS01_PT_P3"
b. Operate command and signals with regard to the switch motion (P1 to P2)
Sensing intermediate state
Signal "TPOS01_PT_P1"
Signal "TPOS01_PT_P2"
Signal "TPOS01_PT_P3"
b. Operate command and signals with regard to the switch motion (P2 to P1)
Sensing Intermediate state
Signal "TPOS01_PT_P1"
Signal "TPOS01_PT_P2"
Signal "TPOS01_PT_P3"
b. Operate command and signals with regard to the switch motion (P3 to P2)
- 962 -
Intermediate
Intermediate
OT1
OT2
Intermediate
Intermediate
OT3
OT4
Intermediate
Intermediate
OT5
OT6
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)