Toshiba GR200 Series Instruction Manual page 1135

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

consists of a binary input circuit (BI1), a number generation function ('Binary selection'
provided in basic functions of the PLC editor), and the signal reception point. That is, when
the B1 switch is closed, a signal enters the BI1 circuit and is carried to the Binary selection;
accordingly the Binary selection, which is programmed to generate a group number '2' in UNIT
when signal '1' is injected in BOOL(BIT), can generates and inject the group number '2' at the
'PLC_Group_ENUM'. Consequently, the Setting function (201400) starts change the group
from number '1' to '2'. Note that changing is only performed during the BI1 is closed in the
example logic; hence, the setting number goes back to '1' when the BI1 is open.
GR200 IED
(+)
(–)
IO_SLOT1 (200B01)
BI1
8001001110
BI1
BI2
8101011110
BI2
Binary input circuits BI1 and BI2
at IO#1 (IO_SLOT1)
1
DIN_BOOL
DO
FID
DTYPE
ST
DID
1
DIN_BOOL
DO
FID
DTYPE
ST
DID
Figure 5.8-2 Example for changing a group setting
Note: Function block for the binary input circuit (Binary input FB) is provided in User
1
library of PLC editor. See the Chapter
"Programmable Logic Controller and PLC editor"
Note: The SEL and RS functions are the basic functions. In the logic, when signal '1'
2
enters the SEL function, value '2' is generated. For more information, see the help
menu on the PLC editor.
Note: For your reference, changing to group3 is performed when value '3' enters. In
3
other words, values '1' to '8' correspond to 'group1' to 'group8', respectively.
Note: This example is designed to change 'group1' to 'group2' or 'group2' to 'group1'.
4
Figure 5.8-3 exemplifies that selecting a group among eight groups is required by the
usage of three BI circuits (i.e., Group 1→Group2, Group3,... Group8).
Binary selection
Entering
Leaving
'1' in BOOL
'2' in UNIT
'0' in BOOL
'1' in UNIT
PLC basic-function
PLC basic-function
(Flip-Flop)
(SEL)
2
SEL
2
RS
Q1
G
SET
IN0
Unit#16#1
RESET1
Unit#16#2
IN1
- 1112 -
201400 314000E1A0
PLC_Group_ENUM
A group number enters
to "Setting function (FunctionID: 201400)"
Unit#16#201400
Unit#16#31
Unit#16#4000E1A0
4
PLC editing
Basic manual
in
attached the PLC software.
6F2S1914 (0.49)
Operation of
changing
3
DOUT_UNIT
FID
ST
DTYPE
DID
DI
GRL200 (Soft 033 & 037)