Toshiba GR200 Series Instruction Manual page 914

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

"DPOS01_OSL_BO_FLG" and "DPOS01_FSL_BO_FLG".
BO connection for "Operate command On/Off"
(iii)
Figure 4.8-44 exemplifies the connection for operate command On/Off. Suppose that connection
with the BOs is achieved by the PLC function using connection points "DPOS01_OEX_BO" and
"DPOS01_FEX_BO"; as a result, the "Operate command On" and the "Operate command Off"
signals are issued at BO3 and BO4 respectively.
Operate logic in DPOS01
"
DPOS01_OEX_BO
(512001 8203011DD3)
Operate logic for
"Operate command
On"
To contact health
check
"
DPOS01_FEX_BO
(512001 8103011DD0)
Operate logic for
"Operate command
Off"
To contact health
check
Figure 4.8-44 Example of operate commands connected with BO3 and BO4 at IO#1
†Note: Table 4.8-18 shows the remaining signals with the exception of
"DPOS01_OEX_BO" and "DPOS01_FEX_BO".
Contact health check
(iv)
The DPOS01 function has a contact health check feature for the BO circuits; hence, the user
is able to connect an output signal to the contact health check function when Fixedlogic is set
for scheme switch [DPOS01-LGXFEOT]†. Consequently, the DPOS01 function can determine
whether the signal has been successfully output from the BO. If a failure is reported, the
DPOS01 function determines that the signal has not been output successfully to the BO; then,
the command On or Off is canceled immediately and the DPOS01 function returns to the "Wait
for a command" stage.
†Note: Table 4.8-34 shows settings for the health check feature in the other DPOS
functions.
"
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO3
"
200B01 310202E11D
Signal captured by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO4
200B01 310203E11D
- 891 -
BO3 and BO4 circuit at IO#1 (Function ID: 200B01)
(200B01_8202021112)
≥1
≥1
&
On
[BO3_CPL]
&
Off
BO3_SOURCE
(
200B01_8302031112)
≥1
≥1
&
On
[BO4_CPL]
&
Off
BO4_SOURCE
6F2S1914 (0.49)
Terminal and
wire
Operate
"
"
BO3
command
On to the
device
DRIVER
BO3
"
"
BO3-RB
(
200B01_8202021113)
To contact health
check
Operate
"
"
BO4
command
Off to the
device
DRIVER
BO4
"
"
BO4-RB
(
200B01_8302031113)
To contact health
check
GRL200 (Soft 033 & 037)