DC voltage monitoring
5.5.3
Threshold voltage for detection/non-detection of power error
(i)
DC voltage is monitored, and a power supply failure can be outputted from the PWS for the
Automatic supervision function. The user should set its failure level for the PWS. See
Automatic supervision function
Table 5.5-5 shows the threshold voltages for detection/non-detection of the power error at the
level high and low. This also shows how to set them with a shunt connector.
Table 5.5-5 Threshold voltage for detection/non-detection of the power error
(a) In the case of DC rated voltage "110-250 Vdc"
Voltage level
High
Typical 170V
Low
Typical 85V
(b) In the case of DC rated voltage "24-60 Vdc"
Voltage level
High
Typical 34V
Low
Typical 19V
Figure 5.5-2 Location of JP4 on the PWS module
for more information.
Threshold voltage for detection/non-detection of the power error
Threshold voltage for detection/non-detection of the power error
- 1086 -
How to set
3
Insert a shunt connector
2
to position"1-2" at JP4
1
3
Insert a shunt connector
2
to position"2-3" at JP4
1
How to set
3
Insert a shunt connector
2
to position"2-3" at JP4
1
3
Insert a shunt connector
2
to position"1-2" at JP4
1
6F2S1914 (0.49)
Chapter
Note
This is
default.
Note
This is
default.