Error terminal configuration (Term ID)
10.5.8
The user can monitor the network configuration between terminals. The error signal is issued
when the erroneous configuration is observed for ten seconds. For monitoring, the user should
set Off for the settings [MSCHK-EN] and set On for the [CHK_TERM_CNF:Sw]. For more
information
about
Communication application
Error level
(i)
Generally, the default error level is set at level 2 (Serious error (Comm)), but the user can
program the level using setting [CHK_TERM_CNF:Lvl]; then, set On for the setting
[CHK_TERM_CNF:Sw]. The manufacturer sets ten (10) seconds to detect the failure; it is reset
with in a second when the failure is cleared.
Error message
(ii)
When the function operates and detects error, an error message can be shown at the LED and
the LCD screen.
Table 10.5-17 Error messages provided by the supervisor in CHK_TERM_CNF
Message and level
Term ID error
Error level
Table 10.5-18 Detailed information in Hexadecimal in CHK_TERM_CNF
Display area
N/A
the
master-slave
relationship,
.
Meaning of the information
Detection for error ID in the network configuration
Serious error (Level 2)
Meaning of the detailed information
(No information is displayed)
- 1311 -
6F2S1914 (0.49)
Relay application:
see
chapter
GRL200 (Soft 033 & 037)