Toshiba GR200 Series Instruction Manual page 1321

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Supervision task of interruption capability on CB
For the supervision of the circuit breaker, the sigma_Iy function is provided so that the broken
current quantities at respective tripping are accumulated. Thereby, the user can monitor the
interrupting capability using the sigma_Iy function. When trip commands are issued, the
sigma_Iy function monitors the maximum current (I at CT primary) in every occurrence of the
fault, the sigma_Iy function accumulates each maximum fault current powered by a parameter
'y'. Thus, the user can find a synthesized broken current value using the sigma_Iy function.
Displaying error message founded by the sigma_Iy function is shown in Table 10.4-1.
Table 10.4-1 Supervision items and error levels for Sigma_Iy
Sec.No.
Supervision items(Screen message)
10.4.1
Sigma Iy error (CHK_SGMIY error)
─────────────────────────────────────────────────────────────────
Note:
The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the "G&T position" whilst
referring to the comparison table below. For more information, see
Table 10.4-2 Comparative table in respective ordering numbers
✓: Applicable
Sec.
Feature
Main features
NA: Not applicable
- 1298 -
Ordering No. at "G&T"
33
37
6F2S1914 (0.49)
Detailed
Error
Info.
Lvl
N/A
3
Appendix: Ordering
.
GRL200 (Soft 033 & 037)
LED
On