Toshiba GR200 Series Instruction Manual page 1193

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Setting
8.3.8
DISTURB_REC(Function ID: 200401)
Setting items
Record Time
Pre-fault Time
Sampling Rate
Interpolate Mode
Trip Trig.SW
DISTURB_REC(Function ID: 200401)
Setting items
Binary Signal1
Binary Sig.Name1
Binary Signal2
Binary Sig.Name2
Binary Signal3
Binary Sig.Name3
......
......
Binary Signal256
Binary Sig.Name256
DRT_LP(Function ID: 4B0001)
Setting items
OC-DRT-EN
OC-DRT
EF-DRT-EN
EF-DRT
UV-DRT-EN
UV-DRT
UVS-DRT-EN
UVS-DRT
Range
Unit
0.1 - 10.0
s Time for disturbance recording
0.1 - 10.0
s Pre-fault time
7.5 / 15
deg Sampling electrical degree for recording
Off / On
– Sampling data interpolated in 15 degree
Off / On
– Operation with the TRC trip command
Range
Unit
(Preferred DataID)
– Logic signal1 for the operation
(Preferred name)
– Name of the logic signal1
(Preferred DataID)
– Logic signal2 for the operation
(Preferred name)
– Name of the logic signal2
(Preferred DataID)
– Logic signal3 for the operation
(Preferred name)
– Name of the logic signal3
......
– ......
......
– ......
(Preferred DataID)
– Mode setting for the detection
(Preferred name)
– Name of the trigger signal768
Range
Unit
1A rating
5A rating
Off / On
– Disturbance Record Trigger OC-DRT enable
0.10 -
0.50 -
OC-DRT relay operating value
A
50.00
250.00
Off / On
– Disturbance Record Trigger EF-DRT enable
0.10 -
0.50 -
EF-DRT relay operating value
A
50.00
250.00
Off / On
– Disturbance Record Trigger UV-DRT enable
5.0 - 130.0
– UV-DRT relay operating value
Off / On
– Disturbance Record Trigger UVS-DRT enable
5.0 - 130.0
V UVS-DRT relay operating value
- 1170 -
6F2S1914 (0.49)
Contents
Contents
Contents
GRL200 (Soft 033 & 037)
Default
Note
3.0
0.3
15
Off
On
Default
Note
See Setting table
in this section
Default
Note
1A
5A
Off
1.00
5.00
Off
0.20
1.00
Off
0.20
Off
51.0

Advertisement

Table of Contents
loading

Table of Contents