Object_reference
Ctrl/GAPC1$SPCSO1$origin
Ctrl/GAPC1$SPCSO1$origin
Ctrl/GAPC1$SPCSO1
Ctrl/GAPC1$SPCSO1
Ctrl/GAPC1$SPCSO1
Ctrl/GAPC1$SPCSO1
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
Figure 4.11-8 orCat attribute mapped into SPCSO1 object of GAPC1
Mapping input data
(iii)
The ASEQ1 function can receive three commands "select, operate, and cancel". Thus, the user
should map the input-point "ASEQ01_CONTROL_REQ ". Table 4.11-12 shows the input-point
" ASEQ01_CONTROL_REQ " and the Object reference "Ctrl/GAPC1$SPCSO1"; the user should
map the input-point to the Object references with attributes CO and CF under FC†. Figure 4.11-9
shows how to map a signal.
†Note: The attribute is defined in the IEC 61850 standard; "CO" stands for "Control"
and "CF" stands for "Configuration" in the functional constraint (FC).
Table 4.11-11 Mapping signals for SPCSO1 object
Attribute
Type
orCat
orCategory
orIdent
Octet64
stVal
BOOLEAN
q
Quality
t
Timestamp
stSeld
BOOLEAN
- 1005 -
FC
Signal Number
ST
523001 300D011008
ST
523001 6A0D011009
ST
523001 000D011001
ST
523001 310D011005
ST
523001 900D011006
ST
523001 000D011D90
6F2S1914 (0.49)
Signal Name
ASEQ01_ORCAT
ASEQ01_ORIDENT
ASEQ01_ACC_EXEC
ASEQ01-QUALITY
ASEQ01_TIME
ASEQ01_STSELD
Drag and drop