Toshiba GR200 Series Instruction Manual page 1012

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

switch [GBI-NELD] is provided to set the number of state-changes so that this function will
start to suppress the signal from this point. The user can set [GBI-TELD] pertaining to the
detection period of the repetitive signals (point A to point C). For example, the user can set the
value "10" for the scheme switch [GBI-NELD]; period A–C is set for the setting [GBI-TELD].
The GENBI function should remove event suppressed operation when the repetitive
signals disappear, (that is, the operation of the device is steady); event suppression operation
is cleared when no repetitive signal is found for a set period. The user can set the period using
scheme switch [GBI-TELR]; this reset operation clears the event suppression function at point
E when the last state change is confirmed at point D. Here, the period D–E is set for the Scheme
switch [GBI-TELR].
The event suppression function is provided for every device; the user should set On for
the scheme switch [SLOT1 GBI01-SPPEN], for example.
Table 4.10-2 Example of event list screened
Event
Off
On
Off
On
Off
On
Off
On
Off
On
On
Table 4.10-2 shows the event list screen. This event list is in response to the signals shown
in Figure 4.10-3. Table 4.10-3 lists the common settings for event suppression. Table 4.10-4
shows the settings for a particular slot.
Table 4.10-3 Common settings for event suppression
Scheme switch
GBI-NELD
GBI-TELD
GBI-TELR
Table 4.10-4 Sets for event suppression in each slot
Scheme switch
SLOT1 GBI01-SPPEN
SLOT1 GBI02-SPPEN
.
Event contents screened
No.1 event
No.2 event
No.3 event
No.4 event
No.5 event
No.6 event
No.7 event
No.8 event
No.9 event
No.10 event suppression SET
Event suppression RESET
Set
Comment
0 – 99 sec
Number of Event lock detect time
1 – 99 sec
Timer of detect event lock
1 – 99 sec
Timer of recovery from event lock
Set
Off / On
SLOT#1 BI-1 Automatic event suppression function
Off / On
SLOT#1 BI-2 Automatic event suppression function
.
- 989 -