Lenovo ThinkSystem SD650 Manual page 222

Hide thumbs Also See for ThinkSystem SD650:
Table of Contents

Advertisement

Automatically notify support
User Action
Complete the following steps:
1. Check if PSU power cord is plugged.
2. Reseat components in the following order, continue down the list if OV fault is not de-asserted:
Power supply, Mid-plane, All Nodes.
3. If PSU 12V UV Fault is still asserted, replace PSU.
• 44 : PS1_12V_AUX_Fault
Power supply is having faulty condition in providing 12V AUX power.
Severity
Critical
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Check if PSU power cord is plugged.
2. Reseat components in the following order, continue down the list if OV fault is not de-asserted:
Power supply, Mid-plane, All Nodes.
3. If PSU 12V AUX Fault is still asserted, replace PSU.
• 45 : PS1_EPOW_Assert
AC power provided to the indicated power supply is lost
Severity
Non-Recoverable
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Make sure PSU power cord is properly plugged in. Check if AC power is stable.
• 46 : PS1_Throttle_Assert
Power supply is having over-current condition.
Severity
Critical
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Make sure PSU power cord is properly plugged in.
2. Un-install node one by one to identify if any of the node is causing the OC condition.
218
ThinkSystem SD650 Dual Node DWC Tray and NeXtScale n1200 DWC Enclosure Messages and Codes Reference