Installation Requirements
Table 2-5 Installation requirements
Item
Equipm
ent
room
door
Floor
Equivale
nt
length
of the
one-
way
pipe
Height
differen
ce
betwee
n the
indoor
and
outdoor
units
Water
supply
Power
require
ments
Note: If the requirements are not met, contact technical support for an
optimized solution.
Issue 04 (2022-11-25)
Specifications
Width ≥ 1.2 m; height ≥ 2.3 m
Bearing capacity ≥ 350 kg/m
≤ 60 m
● If the outdoor unit is placed higher than the indoor unit, the
maximum vertical distance between them is 20 meters.
● If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them is 5 meters.
The inlet water pressure of the humidifier should be 0.1–0.7 MPa,
and the temperature should range from 1°C to 40°C.
The wet film humidifier uses tap water and does not require an
additional water treatment device at the water inlet. The water
requirements are as follows:
● Non-freezing, Nephelometric Turbidity Units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO
Standards for Drinking Water Quality (GB 5749-2006).
Note: Refer to
Leakage circuit breakers are not recommended for the main power
supply route. If a leakage circuit breaker is required by the customer
or local regulations, select the residual current circuit breaker (RCCB)
that is insensitive to single-phase DC pulsation and transient impulse
current.
Copyright © Huawei Digital Power Technologies Co., Ltd.
2
) ≤ 450 mg/L