NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Do not route cables behind the air intake or exhaust vents of the equipment.
Do not directly connect aluminum cables to prevent electrochemical corrosion of
copper and aluminum.
General Requirements
Issue 04 (2022-11-25)
CA UTION
CA UTION
Follow the procedures described in the document for installation, operation,
and maintenance. Do not reconstruct or alter the equipment, add
components, or change the installation sequence without permission.
Install temporary fences or warning ropes and hang "No Entry" signs around
the operation area to keep unauthorized personnel away from the area.
Before installing or removing power cables, turn off the switches of the
equipment and its upstream and downstream switches.
If any liquid is detected inside the equipment, disconnect the power supply
immediately and do not use the equipment.
Before performing operations on the equipment, check that all tools meet the
requirements and record the tools. After the operations are complete, collect
all of the tools to prevent them from being left inside the equipment.
Before installing power cables, check that cable labels are correct and cable
terminals are insulated.
When installing the equipment, use a torque tool of a proper measurement
range to tighten the screws. When using a wrench to tighten the screws,
ensure that the wrench does not tilt and the torque error does not exceed
10% of the specified value.
Ensure that bolts are tightened with a torque tool and marked in red and blue
after double-check. Installation personnel mark tightened bolts in blue.
Quality inspection personnel confirm that the bolts are tightened and then
mark them in red. (The marks should cross the edges of the bolts.)
It is recommended that the three-phase loads be equalized and the neutral-
ground voltage be kept at less than 2 V (ignore this point if no neutral wire is
required) to meet power distribution requirements.
To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits
to telecommunication network voltage (TNV) circuits.
After the installation is complete, ensure that protective cases, insulation
tubes, and other necessary items for all electrical components are in position
to avoid electric shocks.