Space Requirements; Indoor Unit Space Requirements - Huawei NetCol8000-A013 User Manual

In-room air cooled smart cooling product
Hide thumbs Also See for NetCol8000-A013:
Table of Contents

Advertisement

NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
Application
Scenario
Indoor unit
power cable
(optional)
Outdoor unit
power cable
(optional)
Signal cable to
the indoor and
outdoor units
(optional)

3.3 Space Requirements

3.3.1 Indoor Unit Space Requirements

Equipment Room Requirements
Issue 04 (2022-11-25)
Specifications
Electrical power cable, 600 V/1000 V,
ZA-RVV, 5 x 6 mm
wires), 46 A, outdoor cable, CE
Naked crimping terminal: OT, 6 mm
M6, 50 A, tin plating, 12-8 AWG
Electrical power cable, 600 V/1000 V,
ZA-RVV, 3 x 6 mm
wires), 46 A, outdoor cable, CE
Naked crimping terminal: OT, 6 mm
M6, 50 A, tin plating, 12-8 AWG
Electrical power cable, 300 V, SJTW, 3 x
16 AWG, black (three core wires), 10 A,
shielded outdoor cable, UL
Naked crimping terminal, single-wire
cord end terminal, 1.5 mm
To ensure that the environment control system in the smart cooling product
room works properly, take moisture-proof and thermal insulation measures.
The equipment room should have good heat insulation, and the walls and
floor should be protected against moisture. The moisture-proof layer of the
ceiling and wall must be made of polyethylene film. The paint on the concrete
wall and floor must be moisture-proof.
Incoming outdoor air may increase the load of system heating, cooling,
humidification, and dehumidification. Therefore, it is recommended that
outdoor air be prevented from entering the equipment room. (The incoming
outdoor air should be less than 5% of the entire indoor airflow. All doors and
windows should be closed and the gap should be minimal.)
Copyright © Huawei Digital Power Technologies Co., Ltd.
2
, black (five core
2
,
2
, black (three core
2
,
2
, 16 A, Red
3 System Installation
Remarks
Cable should not
be lighter than
normal PVC
sheathed flexible
cord (IEC 60227
53). The length is
determined by site
survey.
Delivered with the
fittings
Cable should not
be lighter than
chloroprene rubber
armored flexible
cord (IEC 60245
57). The length is
determined by site
survey.
Delivered with the
fittings
The length is
determined by site
survey.
Delivered with the
fittings
39